10-2. ENGINE
ELECTRONIC CONTROL
MODULE (EECM). (cont.)
(b) Move MASTER SWITCH to
RUN position. All lights shouId be off.
NOTE
Read step (c) completely before per-
forming step (c).
(c) Move MASTER SWITCH to
START position.
The STARTER light should
come on.
Quickly increase function generator
to a frequency between 2900 and 3200 Hz before
EECM timeout.
During frequency increase,
IGNITION and FUEL Iights will come on and then
STARTER and IGNITION lights will go off. The
FUEL light should remain on. This should happen
between 1965 and 2059 Hz.
(d) Increase function generator
frequency slowly until READY TO LOAD light
comes on and FUEL light should remain on.
This should happen between 3287 and 3421 Hz.
(e) Move
CONTACTOR switch
momentarily to the CLOSED position. CONTACT-
OR ENABLE light should come on.
(f)
Move
OVERLOAD
switch
to
ON position. The OVERLOAD light should come
on and all other lights should go off.
(g) Move OVERLOAD switch to
OFF position.
The OVER LOAD light should
remain on.
(h) Move MASTER SWITCH to
OFF position. All lights should go off.
(i) Any discrepancy noted during
the above procedure,
Refer to Table 2-4, Mal-
function 8.
(16) Generator undervoltage fauIt test.
(a) Adjust function generator to a
frequency between 0 and 200 Hz and adjust
millivolt source to .96 to 1.20 millivolts.
(b) Move MASTER SWITCH to
RUN position. All lights should be off.
10-14.2
Change 1
NOTE
Read step (c) completely before per-
forming step (c).
(c) Move MASTER SWITCH to
START position,
The STARTER light should
come on. Quickly increase function generator to a
frequency between 2900 and 3200 Hz before
timeout.
During frequency increase, IGNITION
and FUEL lights will come on and then STARTER
and IGNITION lights will go off. The FUEL light
should remain on. This should happen between
1965 and 2059 Hz.
(d) Increase function generator
frequency slowly until READY TO LOAD light
comes on and FUEL light should remain on. This
shouId happen between 3287 to 3421 Hz.
(e) Move
CONTACTOR switch
momentarily to the CLOSED position CONTACT-
OR ENABLE light should come on.
(f) Move UNDERVOLT switch to
ON position.
The UNDERVOLT light should
come on and all other lights should go off.
(g) Move UNDERVOLT switch to
OFF position.
The UNDERVOLT light should
remain on.
(h) Move MASTER SWITCH to
OFF position. All lights should go off.
(i) Any discrepancy noted during
the above procedure.
Refer to Table 2-4, Mal-
function 8.
(17) Fuel pump control test.
(a) Adjust function generator to a
frequency between 0 and 200 Hz and adjust
millivolt power source to .96 to 1.20 millivolts
(K-type thermocouple equivalent output). Connect
Oscilloscope to EECM test fixture (pump output
terminal Fig 10-1).
(b) Move MASTER SWITCH to
RUN position. All lights should be off.
NOTE
Read steps (c) and (d) completely before
performing steps (c) and (d).