4-29. SLAVE RECEPTACLE.
c.
Insta llation.
(1) Install slave
in output/slave housing
(cont)
receptacle (11)
(12) and secure
with screws (8), washers (9), and
self-locking
nuts (10).
Torque to
74-82 inch pounds (8.4-9.3 Nm).
(2) Install
slave
receptacle
leads (4) on feedthrough terminals (7)
and secure with washers (6) and nuts
(5).
Torque nut on 3/8 inch stud to
200-275 inch pounds (22.6-31.1 Nm).
Torque nut on 1/2 inch stud 500-650
inch pounds (56.5-73.4 Nm).
(3) Install output/slave housing
access
cover
(3) and secure with
washers (2) and screws (1).
Torque to
24-36 inch pounds (2.7-4 Nm).
(4) Stow power cable on cable
support assembly.
(5) Connect battery cable plug
connector to battery.
4-30. GENERATOR
ELECTRONIC
CONTROL
MODULE.
Maintenance of the generator
electronic
control
module
(GECM)
(figure 4-17) consists of replacement.
When testing/troubleshooting
proce-
dures isolate the GECM as the cause of
a malfunction, remove the GECM and send
to direct
support
maintenance
for
repair.
a.
Removal.
WARNING
To prevent injury, ensure that
battery
is disconnected before
performing
maintenance
on
electrical components.
(1)
connector
4-74
Disconnect battery cable plug
from battery.
(2) Open control
panel
access
door.
(3) Loosen turnlock fasteners and
open control panel.
(4) Tag and disconnect cables
from GECM connectors Jl, J2, and J3.
(5) On
underside of
control
fender, remove nuts (1) and washers (2).
(6) Remove capscrews
(3)
that
secure GECM (4) in control fender.
(7) Lift GECM (4) out of control
fender.
b.
Installation.
(1) Place GECM (4) in control
fender.
Ensure that mounting holes are
alined.
(2) Secure with capscrews (3),
washers (2),
and, nuts (1).
Torque to
74-82 inch pounds (8.4-9.3 Nm).
(3) Connect
cables to
GECM
connectors Jl, J2, and J3.
(4) Close
control
panel
and
secure with turnlock fasteners.
(5) Close control
panel
access
door.
(6) Connect battery cable plug
connector to battery. -
4-31.
CIRCUIT BREAKER.
See
location of circuit breaker
control
panel.
Maintenance
circuit breaker (figure 4-18)
of testing and replacement.
FO-1 for
(CB1) on
of the
consists