TM 5-6115-590-12
(3) Generators
and
Electrical
Power
Chassis
Assemblies. The 60 Hz and 400 Hz generators are
driven by the gas turbine engine dual pad gearbox. The
400 Hz generator is cooled by air supplied from a
cooling air fan driven by the engine accessory drive.
The 400 Hz generator is a 120 KVA brushless, self
excited generator providing three phase, 120/208V
AC, 400 Hz power The 60 Hz generator is a 12-5 KVA
brushless, self-excited generator providing single phase,
120/240V AC. 60 Hz power. The electrical power
chassis assemblies include automatic control, and
protective and regulating components for both the 60 Hz
and 400 Hz AC electrical systems and the 24V DC
electrical systems.
Change 6 1-8.1 (1-8.2 Blank)