Section IV. TROUBLESHOOTING
3-5. GENERAL.
a.
Table
3-3 provides
trouble-
shooting information for locating and
correcting problems that may develop in
the generator set.
Each malfunction
for an individual component, unit, or
system is followed by a list of tests
or Inspections that will help determine
probable causes and corrective actions
to take.
Perform the tests/inspections
and corrective actions in the order
listed.
b. This manual
cannot list all
malfunctions that may occur.
If a
malfunction is not listed or cannot be
corrected by listed corrective actions,
notify supervisor.
NOTE
Before using this table, ensure
that all applicable operating
checks have been performed.
Table 3-3. Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
STARTER ROTATES ENGINE, BUT COMBUSTION DOES NOT OCCUR.
Step 1.
Check to ensure adequate fuel supply.
Fill fuel tank.
Step 2.
Unit still fails to operate.
Refer to next higher level of maintenance.
2.
MASTER SWITCH IS PLACED IN THE START POSITION, BUT ENGINE DOES NOT ROTATE.
Step 1.
Check that
Refer to
Step 2.
Check that
Press DC
no malfunction indicator light is on.
higher level of maintenance if malfunction light is on.
DC CIRCUIT BREAKER reset button is pressed in.
CIRCUIT BREAKER reset button to reset.
Step 3.
Check battery cable plug connector.
Tighten battery connector.
Step 4.
Unit still fails to operate.
Refer to next higher level of maintenance.