TM 55-2835-208-23
2-6 CLEAN AND INSPECT EXTERNAL LINES AND FITTINGS (Continued)
2-6
Note
1.
2.
3.
4.
If disassembly is required
to further inspect for
cause of leakage, refer to
Task 2-7.
Reinstall in
accordance with Task 2-8.
Inspect
for
signs of
fuel
leakage around
coupling
nuts
(1).
If there is a sign of
leakage,
check
coupling
nut
(1) for tightness. Tighten if
loose.
Dry-cleaning solvent
(E20) is flammable and
toxic.
It can irritate
skin and cause burns.
Use only in well-
ventilated area, away
from heat and open
flame.
Wear gloves.
In case of contact,
immediately flush
skin or eyes with
water for at least
15 minutes. Get
medical attention
for eyes.
Wipe external lines and fitt-
ings with a clean cloth (E13)
moistened with
dry-cleaning
solvent (E20).
Inspect
all
tube
assemblies
(2) for dents,
kinks, or
cracks.
There
shall be no
damage.
Inspect fittings (3) and nuts
(4) on bulkhead fittings for
tightness.
If loose, tighten.
GO TO NEXT PAGE
2-14